Chapter 13
Install and inspect one complete masonry water-management mockup at a base, opening, or shelf-angle condition, with continuous flashing, correctly formed end dams, an open drainage cavity, and functioning weeps.
These cues appear at the point of work. They identify safety, code, manufacturer, and measurement issues before they become concealed water-management failures.
Task-specific safety guidance for ordinary flashing and cutting hazards.
Serious injury, structural failure, or major water damage is possible.
Practical work-area safety: access, footing, lighting, and housekeeping.
Local requirements vary. Verify permit, inspection, and jurisdictional rules.
Follow product-specific instructions for flashing, tapes, primers, and weeps.
Lap, slope, spacing, and clearance guidance.
This chapter qualifies you to install and inspect one complete masonry drainage mockup: the flashing, end dams, cavity drainage material, and weep system that carry incidental moisture out of a masonry wall before it can reach the structure. The finished work product is one documented base, opening, or shelf-angle drainage mockup with continuous flashing, formed end dams, an open cavity, and functioning weeps, verified against the approved wall section.
This chapter treats flashing and weeps as a single connected system, not as separate accessories. A flashing lap that reverses direction, an end dam that is missing, a cavity bridged with mortar droppings, or a weep spaced incorrectly all defeat the same drainage path. You will mark every flashing and weep location from the approved wall section, install compatible materials in the correct lap sequence, form end dams at every termination, keep the cavity open, and install weeps aligned with the flashing before any veneer or wall work conceals these details.
This is the thirteenth chapter in the book. It depends on the readiness plan from Chapter 1, the controlled work area from Chapter 2, and the wall layout from Chapter 4, and it supplies the flashing and weep details that Chapter 11 and Chapter 12 install veneer around and that the Chapter 20 capstone must reproduce in full.
Every veneer, cavity wall, and shelf-angle transition in this book depends on the flashing and weep system built here. Chapter 11 installs brick veneer directly on top of the base flashing and weeps this chapter forms, and Chapter 12 relies on the same water-management logic when the veneer type is stone. The photograph-before-concealment discipline you practice here — documenting laps, end dams, and weeps before veneer covers them — is the same discipline the Chapter 20 capstone inspection requires at final acceptance.
The stop-work judgment you use here — refusing to seal a reversed lap, a missing end dam, or a blocked weep with sealant rather than correcting the detail — carries into every later chapter that touches moisture management, including Chapter 15 crack repair and Chapter 19 cleaning and sealing.
This chapter covers:
This chapter does not authorize the learner to:
Any flashing, end-dam, cavity, or weep condition that fails the inspection in this chapter must be corrected and reinspected before veneer or wall work conceals it.
Establish these references before any flashing or weep is installed, and use them consistently across the mockup.
| Term | Definition |
|---|---|
| Back leg | The vertical portion of base flashing that turns up behind the WRB or backup wall to prevent water from tracking behind the flashing |
| End dam | A formed or applied upturn at the end of a flashing run that prevents water from flowing off the end of the flashing into the wall |
| Shingle lap | The overlap sequence in which each higher flashing or WRB course overlaps the course below it, so water always sheds outward and downward |
| Drainage cavity | The open air space behind veneer or cladding that carries incidental moisture down to the flashing and out through the weeps |
| Weep | An opening in the mortar joint or flashing system, at the specified spacing, that allows drainage water to exit the cavity above the flashing |
Before beginning installation, record the selected mockup and its controlling documents on the Flashing and Weep Inspection Log:
Mockup location: ______ (base / opening / shelf-angle) Wall section reference: ____________
Flashing material and manufacturer: ____________ Weep type and spacing per drawing: ____________
Date installed: ____________ Installer name: ____________
Every flashing and weep detail in this book, from a single base condition to the full Chapter 20 capstone, depends on the same sequence taught here: identify every water-entry point, select compatible materials, integrate flashing with the WRB in shingle-lap order, form end dams, keep the cavity open, install weeps aligned with the flashing, and inspect the complete system before it is concealed.
Treat every flashing run in this chapter as one connected water-management system rather than a series of separate patches. A back leg without a matching end dam, an end dam without a matching weep, or a weep installed above rather than at the flashing elevation each defeats the system at the point of the missing connection. Verify the full path from entry point to exterior outlet before installing the next component.
Verify every flashing lap length and every weep spacing against the approved wall section before installation, and record the as-built measurement on the Flashing and Weep Inspection Log. Do not estimate a lap or spacing from general trade practice when the wall section specifies an exact value.
Do not allow veneer, brick, block, stone, or any wall finish to conceal a flashing, end-dam, cavity, or weep detail before the Step 20 inspection has passed and been photographed. A concealed, unverified detail cannot be corrected without demolition, and a failed detail that is concealed anyway creates a hidden moisture path into the structure.
Wear cut-resistant gloves and eye protection when cutting or forming metal flashing with tin snips or a hand seamer. Support flashing stock on a stable work surface while cutting. Keep hands clear of formed edges until they are dressed.
Confirm weep type, spacing, and required flashing locations against adopted code and the approved wall section before installation. Requirements vary by jurisdiction and wall assembly; do not apply the spacing or flashing locations from a prior project without verifying them for the current wall section.
RM-073 – RM-078
Installation / Water Management / Inspection
Deliverable: one complete base, opening, or shelf-angle drainage mockup consisting of substrate preparation, base or through-wall flashing with back leg and shingle-lap WRB integration, formed end dams at every termination, cavity drainage material or mortar-dropping control, weeps installed at the specified spacing and aligned with the flashing, termination or counterflashing where specified, and a documented inspection of every detail before concealment.
| Component | Quantity | Material | Location / Detail | Preparation |
|---|---|---|---|---|
| Base flashing | Per mockup length, as specified in the wall section | Approved flashing membrane or metal as specified | Base of wall or cavity | Cut to length with back leg and outward slope per drawing |
| Through-wall flashing | Per opening, lintel, or shelf-angle location specified | Approved flashing membrane or metal as specified | Above lintels, openings, shelf angles, interruptions | Cut to length with required laps |
| End dams | One per flashing termination | Formed flashing material or compatible end-dam accessory | Every flashing end and termination | Formed or applied per manufacturer instructions |
| Cavity drainage material | Per cavity area specified | Mortar-dropping control or drainage mat as specified | Full cavity height above flashing | Cut and fastened per manufacturer instructions |
| Weeps | Per spacing specified in the wall section | Open-head weeps, tubes, wicks, or proprietary weep accessories as specified | Aligned with flashing at specified spacing | Installed without mortar or sealant obstruction |
Use the terms defined in the Reference Conventions table above. Additionally: the exterior face of flashing is the surface exposed to the cavity or exterior air; the interior leg is the portion integrated with the WRB or backup wall; upslope and downslope refer to the direction of water flow along the flashing as installed.
| Check | Standard |
|---|---|
| Back leg and slope | Back leg height and outward slope match the approved wall section; verified with a level before cavity material is installed |
| Shingle lap | Every lap overlaps the course below it in the direction of water flow; no reverse lap present at any transition |
| End dams | Formed or applied at every flashing termination; no gap through which water could bypass the end of the flashing |
| Cavity condition | Open from top to weep elevation; free of mortar bridging, droppings, or obstruction of the drainage material |
| Weep spacing and alignment | Weeps installed at the spacing specified in the wall section and aligned with the flashing elevation; no weep filled with mortar or sealant |
| Sealant use | Limited to locations identified by manufacturer instructions; never used to correct a missing flashing, end dam, or blocked weep |
| Photographic record | Every flashing lap, end dam, cavity condition, and weep location photographed before concealment by veneer or wall work |
Inspect every flashing and weep mockup using the same checks regardless of the selected location.
Complete the Flashing and Weep Inspection Log in the Inspection Checklist section below before releasing the mockup to veneer work.
Probable cause: a reverse lap directed water behind the flashing instead of over it.
Confirmation: inspect the lap sequence at the stained location and compare it against the shingle-lap requirement.
Correction: remove the affected flashing section and reinstall it in the correct shingle-lap order with compatible tape or sealant at the reworked lap only.
Reinspection: reinspect the corrected lap and reperform the drainage observation if one was part of the original acceptance.
Probable cause: mortar was allowed to enter the weep during installation, or a weep was sealed to "clean up" the appearance of the wall.
Confirmation: probe the weep opening; a blocked weep will not allow a probe to pass through to the cavity.
Correction: clear the obstruction or replace the weep accessory; never seal a weep with mortar or sealant as a substitute for clearing it.
Reinspection: confirm the weep is fully open and aligned with the flashing before concealment.
Probable cause: mortar-dropping control was omitted, damaged, or installed after masonry work had already begun above the cavity.
Confirmation: inspect the cavity from the weep opening or an accessible course for visible mortar bridging between the backup wall and the veneer or unit face.
Correction: remove the bridging material without damaging the flashing, and install or repair the cavity drainage material before further masonry work continues.
Reinspection: confirm the cavity is open from top to weep elevation before veneer work resumes.
Probable cause: the flashing run was cut to length without forming or applying the required end dam.
Confirmation: inspect every flashing end and termination for a formed upturn or applied end-dam accessory.
Correction: form or apply the end dam using the manufacturer-specified method before the location is concealed.
Reinspection: confirm the end dam is continuous and photograph it before veneer work covers the location.
Probable cause: veneer or wall work proceeded before the Step 20 inspection and photographic record were completed.
Confirmation: compare the Flashing and Weep Inspection Log against the photographic record; a missing photograph or inspection entry for a now-concealed location confirms premature concealment.
Correction: stop veneer or wall work at the affected location and, where the detail cannot be verified without removal, remove the concealing work to inspect and photograph the flashing and weep detail underneath.
Reinspection: complete the inspection and photographic record before veneer or wall work resumes at that location.
This chapter ends with a documented, verified drainage mockup, not a visually finished wall with unverified details underneath.
| Competency | Independent Pass Standard | Not Demonstrated | With Assistance | Independently |
|---|---|---|---|---|
| RM-073 | Correctly identifies and marks every flashing and weep location from the approved wall section before installation begins | |||
| RM-074 | Installs base flashing with the required back leg, outward slope, WRB integration, and end dams, verified with a level | |||
| RM-075 | Installs through-wall flashing above lintels, openings, shelf angles, and interruptions with correct laps and end dams | |||
| RM-076 | Forms weep holes at the specified spacing, aligned with flashing, and free of mortar or sealant obstruction | |||
| RM-077 | Maintains the drainage cavity free of mortar bridging and mortar-dropping obstruction throughout installation | |||
| RM-078 | Inspects and photographs laps, adhesion, end dams, slope, outlets, cavity condition, and weeps before concealment |
Mark one column per competency. Only Demonstrated Independently awards the competency; Demonstrated with Assistance authorizes additional supervised practice but does not complete the requirement.
| Item | Finding | Pass / Deficient | Correction | Reinspected (Date) |
|---|---|---|---|---|
| Base flashing back leg and slope | ||||
| Shingle lap sequence | ||||
| End dams | ||||
| Through-wall flashing | ||||
| Cavity drainage material and condition | ||||
| Weep spacing and alignment | ||||
| Termination or counterflashing | ||||
| Photographic record complete |
Drainage observation performed: ______ (Y/N) Result: ____________
Released to veneer work: ______ (Y/N) Date: ____________ Inspector name: ____________
With installation complete, review the Flashing and Weep Inspection Log against the Acceptance Standards table and confirm every lap, end dam, cavity condition, and weep has been recorded with a measurement and photograph. Confirm every Deficient item has a documented correction and reinspection record before the mockup is released to veneer work. A mockup with any unresolved reverse lap, missing end dam, blocked weep, or bridged cavity must not be concealed until the deficiency is corrected and reinspected.
You have completed the thirteenth chapter in the residential masonry sequence: installing weep holes, flashing, and masonry drainage details. This chapter required you to identify flashing locations (RM-073), install base flashing (RM-074), install through-wall flashing (RM-075), form weep holes (RM-076), maintain the drainage cavity (RM-077), and inspect water-management details (RM-078).
You now have a documented masonry drainage mockup with continuous flashing, formed end dams, an open cavity, and functioning weeps, verified and photographed before concealment. This mockup, and the inspection log describing it, carries directly into the next chapters: the brick and stone veneer installations in Chapter 11 and Chapter 12 depend on the exact flashing and weep system you built and verified here.
File your completed Flashing and Weep Inspection Log and photographs with the approved wall section for this project. You will reference this exact drainage system throughout the rest of this book.