Chapter 6
Build one stepped block corner and one T-intersection practice assembly, controlling course height, bond, plumb, rack-back, ties or anchors, and wall-line transfer to intersecting work.
These cues appear at the point of work. They identify safety, code, manufacturer, and measurement issues before they become rework, structural risk, or moisture damage.
Task-specific safety guidance for ordinary corner and intersection work.
Serious injury, structural failure, or major damage is possible.
Practical work-area safety: access, footing, lighting, and housekeeping.
Local requirements vary. Verify permit, inspection, and jurisdictional rules.
Follow product-specific instructions for units, mortar, ties, and reinforcement.
Square, plumb, rack-back, and course-height guidance.
This chapter qualifies you to build a plumb, square, bonded concrete-masonry corner lead and a T-intersection practice assembly. The finished work product is one stepped corner lead and one intersecting-wall assembly, each built to the approved bond pattern, rack-back detail, course elevations, and tie or reinforcement schedule, and each inspected before mortar hardens.
Chapter 5 taught you to build a straight nonstructural block practice wall using bed joints, head joints, and a story pole. This chapter extends that skill to the point where two walls meet — a corner, where one wall turns a angle, and an intersection, where a second wall joins the first as a T. Corners and intersecting walls control the line and course elevation for every unit laid between them; a corner lead built out of square or out of level carries that error into every wall section that follows it.
Nothing in this chapter authorizes structural or load-bearing corner and intersection work beyond the approved practice-assembly detail supplied for this project. This is nonstructural practice work built to demonstrate bond, plumb, square, rack-back, and tie placement.
Chapter 4 established the layout, corner references, and story pole for a masonry wall. Chapter 5 applied bed joints, head joints, and course control to a straight run. This chapter applies that same course control to the two conditions every real block wall eventually reaches: a turned corner and an intersecting wall. The lead you build here is what a mason's line is stretched from in every subsequent wall section, so its square, plumb, and elevation control the accuracy of everything built between leads.
Chapter 7 depends on the reinforcement and grouting skills you demonstrate placing ties and anchors at the intersection in this chapter. Chapter 9 repeats this corner-and-lead logic in brick. The Chapter 20 capstone assumes the learner can build and check a corner lead without supervision.
This chapter covers:
This chapter does not authorize the learner to:
Any corner or intersection that fails square, plumb, bond, or tie inspection during this chapter must be corrected before the mortar hardens, or removed and rebuilt.
Establish these references before laying the first corner unit, and use them consistently through the lead and intersection.
| Term | Definition |
|---|---|
| Lead | The corner or end section of a wall built up several courses ahead of the intervening wall, used to establish line and course elevation |
| Rack-back | The stepped pattern in which each successive course of a lead is set back from the course below it, following the approved bond |
| Corner arris | The vertical outside edge formed where the two wall faces meet at the corner |
| Intersecting-wall tie | A metal tie, bond unit, or anchor connecting an intersecting wall to the primary wall at a T-intersection, per the approved detail |
| Tooth | An unapproved, unsupported step or interlock at an intersection not shown in the approved detail; not permitted in this chapter |
Before beginning layout, record the assembly identity and controlling documents directly on the work order:
Assembly name: ______ Corner angle: ______ Intersection type: ______ (T-intersection / other, per approved detail)
Approved corner/intersection detail on hand: ______ (Y/N) Tie or anchor product specified: ____________ Wall thickness: ______ Height limit for this practice assembly: ______
Date built: ____________ Mason name: ____________
A corner lead is built to establish two things that the rest of the wall depends on: the corner angle and the course elevation. Every unit laid in the intervening wall is checked against the line stretched from the lead, so an error in the lead is transferred into the entire wall run. An intersection adds a third requirement — a tie or anchor connection between two walls that must accommodate differential movement while transferring the specified load or restraint, exactly as the approved detail requires.
Do not create an unapproved tooth or unsupported intersection. If the approved detail does not show a specific tie, anchor, bond-unit, or rack-back arrangement for a condition encountered in the field, stop and obtain the missing detail rather than improvising an interlock. Do not build the lead more than the number of courses above adjacent wall work permitted by the approved detail; an overextended lead is unsupported and unstable.
Verify the corner angle with a framing square or diagonal measurement immediately after the first-course corner unit is set, before laying the second course. Recheck the diagonal at each lead course. A corner angle error compounds with height; catch it at the base.
Do not build the corner lead more than the number of courses above adjacent wall work permitted by the approved detail. An overextended, unsupported lead can be struck or can shift under its own weight before adjoining courses are laid. Stop work and bring adjacent wall sections up to the lead before continuing higher.
Checking plumb on both wall faces and the corner arris requires moving around the lead repeatedly. Keep the work area at the base of the lead clear of loose units, tools, and mortar-board debris so this movement does not create a trip hazard.
Confirm the specified intersecting-wall tie, bond unit, or anchor product and its spacing against the approved detail and manufacturer instructions before installation. Tie type and spacing requirements vary by wall system and jurisdiction; do not substitute a different product or spacing without written approval.
Install intersecting-wall ties, bond units, or anchors using the embedment depth, orientation, and fastening method stated in the manufacturer's instructions for the specified product. Do not bend, cut, or reposition a tie or anchor in a way the manufacturer's instructions do not permit.
RM-031 – RM-036
Layout / Construction / Inspection
Deliverable: one stepped concrete-masonry corner lead built to the approved corner detail, and one T-intersection built to the approved intersection detail, each with verified square, plumb on both faces and the corner arris, correct bond and rack-back, specified ties or anchors installed at the intersection, verified course elevations against the story pole, and a completed inspection record.
| Component | Quantity | Material | Finished Size | Preparation |
|---|---|---|---|---|
| Corner-lead units | Per approved detail component count | Concrete masonry unit as specified | Per specified unit dimensions | Dry-laid and adjusted before mortar is spread |
| Intersection units | Per approved detail component count | Concrete masonry unit as specified | Per specified unit dimensions | Dry-laid and adjusted before mortar is spread |
| Intersecting-wall ties or bond units | Per approved tie schedule and spacing | Corrosion-resistant tie, bond unit, or anchor as specified | Per manufacturer instructions | Installed at the specified course and embedment |
| Joint reinforcement (if specified) | Per approved detail | As specified in the approved detail | Per specified width and length | Placed in the bed joint at the specified courses |
| Joint / Location | Fastener or Hardware | Spacing / Embedment | Installation Direction | Seating Condition |
|---|---|---|---|---|
| T-intersection tie course(s) | Intersecting-wall tie or bond unit as specified in the approved detail | Per the approved course spacing and manufacturer embedment depth | Per manufacturer instructions; do not reverse or invert the specified orientation | Fully embedded in the mortar joint with no exposed unbedded length |
Do not treat "tie" or "anchor" as a complete specification. Identify the exact product, spacing, and embedment from the approved detail and manufacturer instructions before installation.
| Check | Standard |
|---|---|
| Corner angle / square | Diagonal measurements match within the tolerance stated in the approved detail; if none is stated, record the measured deviation and correct before continuing rather than estimating a tolerance |
| Plumb | Both wall faces and the corner arris plumb within the tolerance stated in the approved detail, checked at every course |
| Bond and rack-back | Bond pattern and rack-back step match the approved detail at every course; no aligned vertical joints across courses unless the design permits them |
| Course elevation | Each course height matches the story pole mark for that course |
| Intersecting-wall ties | Installed at the specified course, spacing, and embedment, fully bedded in mortar, with no substitution of product or orientation |
| Lead height above adjacent work | Does not exceed the number of courses stated in the approved detail before adjacent wall work is brought up to match |
| Tooth or unsupported intersection | Not present; every intersection detail matches the approved drawing exactly |
Inspect every corner and intersection assembly using the same checks regardless of the specific bond pattern specified.
Complete the Corner and Intersection Inspection Record below before stretching a mason's line to intervening wall sections.
Probable cause: the first-course corner unit was set without verifying square against both baselines, or the diagonal measurement was not rechecked at subsequent courses.
Confirmation: measure the diagonal at the current course and compare it against the approved tolerance; a growing deviation confirms an uncorrected first-course error.
Correction: if the mortar is still workable, reset the affected units to correct square; if hardened, remove and rebuild the lead from the first course showing the error.
Reinspection: recheck the diagonal at every course from the corrected point upward before continuing.
Probable cause: units were tapped to line without checking plumb at each course, allowing a small lean to accumulate.
Confirmation: check the level along the full height of the affected face and at the corner arris; compare the reading against the story pole and the acceptance tolerance.
Correction: reset the out-of-plumb units while mortar remains workable; do not attempt to correct accumulated lean by tapping only the top course.
Reinspection: recheck plumb on both faces and the arris at every course above the correction.
Probable cause: the rack-back step was estimated by eye rather than measured against the approved detail, or units were laid in running bond where the detail specified a different pattern.
Confirmation: compare the head-joint offset and rack-back step of each course against the approved detail's bond diagram.
Correction: remove and relay the courses that do not match the specified pattern.
Reinspection: recheck bond and rack-back at every course from the correction point upward.
Probable cause: the tie schedule was not checked against the approved detail before laying the course, or a different tie or anchor was used because the specified product was not on hand.
Confirmation: compare the installed tie type, course, spacing, and embedment against the approved detail and manufacturer instructions.
Correction: if mortar is still workable, remove the unit, install the correct tie, and relay the unit; if hardened, remove and rebuild the affected course with the specified tie.
Reinspection: verify tie type, course, spacing, and embedment at every intersection course before continuing.
Probable cause: the lead was continued upward without bringing the intervening wall sections up to match, exceeding the permitted course difference in the approved detail.
Confirmation: count the course difference between the lead and the highest adjacent wall section and compare it against the approved detail's limit.
Correction: stop building the lead higher and lay the intervening wall sections up to the permitted course difference before continuing.
Reinspection: recheck the course difference before resuming work on the lead.
This chapter ends with an inspected, cured corner lead and intersection, not an assembly left to cure unchecked.
| Competency | Independent Pass Standard | Not Demonstrated | With Assistance | Independently |
|---|---|---|---|---|
| RM-031 | Sets the first-course corner unit to level, square, and elevation and builds the lead one course at a time | |||
| RM-032 | Racks back each successive course of the lead in the approved stepped pattern while maintaining bond and overlap | |||
| RM-033 | Installs intersecting-wall ties, bond units, reinforcement, or anchors exactly as specified at the correct course, spacing, and embedment | |||
| RM-034 | Checks and maintains plumb on both wall faces and the corner arris at every course | |||
| RM-035 | Maintains the specified bond pattern and overlap through the corner and intersection | |||
| RM-036 | Inspects corner square, plumb, bond, rack-back, ties, and course height and corrects drift before mortar hardens |
Mark one column per competency. Only Demonstrated Independently awards the competency; Demonstrated with Assistance authorizes additional supervised practice but does not complete the requirement.
| Item | Finding | Deficient | Correction | Reinspected (Date) |
|---|---|---|---|---|
| Corner angle / square | ||||
| Plumb — face 1 | ||||
| Plumb — face 2 | ||||
| Plumb — corner arris | ||||
| Bond and rack-back | ||||
| Intersecting-wall ties | ||||
| Course elevation | ||||
| Lead height above adjacent work |
Final result: ______ (Pass / Corrected and Repassed / Rebuild Required) Date: ____________ Mason name: ____________
With the corner lead and intersection complete, review the Corner and Intersection Inspection Record against the Acceptance Standards table and confirm every course has a recorded square, plumb, bond, and elevation result. Confirm every installed intersecting-wall tie matches the approved product, course, spacing, and embedment. Correct any recorded deficiency while the mortar remains workable, or remove and rebuild the affected courses. Do not stretch a mason's line from the lead to guide intervening wall work until the final result is recorded as Pass or Corrected and Repassed.
You have completed the sixth chapter in the residential masonry sequence: building block wall corners and intersections. This chapter required you to lay block corners (RM-031), rack back courses (RM-032), tie intersecting walls (RM-033), maintain plumb (RM-034), maintain bond pattern (RM-035), and inspect corner strength and alignment (RM-036).
You now have a plumb, square, bonded corner lead and a correctly tied T-intersection, each verified against the approved detail and documented on the inspection record. This lead is the reference every intervening wall course depends on, and the tie installation practiced here carries directly into Chapter 7, where you place reinforcement and grout in a concrete-masonry wall section.
File your completed Corner and Intersection Inspection Record with the Chapter 4 layout documentation for this project. You will reference this exact lead and intersection throughout the remaining block-masonry chapters.